NO. 11 FILTER SEPARATOR CONTROLS - PART 2 AUG. 1976
TESTING
Revised Nov. 1996
Did you know that to this very day there are oil companies and airlines who
never test the control valves on filter separators? if you never test the
float pilot valve, how can you know that it will operate if a big slug of
water comes along? Are you saying that you never have water anyhow? At this
point I make a rude remark and remind you that you have that equipment
to save your skin in the event that something
unexpected happens.
One of the humorous experiences I have had, in traveling from airport to
airport these many years, was with a customer who was vigorously resisting
spending money to change long overdue elements in his filter separator, "because
we never have water in our fuel". We were standing beside the filter and
right after he finished talking, a stream of foul dark water started to gather
around his shoes. The automatic water drain valve had opened.
And then there are the operators who put plugs in the outlet ports of their
automatic water drain valves. Many of you have manual valves that are kept
closed upstream or downstream of the automatic water valve. If you do this
to stop leaks, you must realize that you have completely eliminated this
factor of safety. In fact, if the vent tube is connected to a plugged drain
valve, you will prevent the slug valve from operating correctly. Why not
repair the leak? Every manufacturer can supply spare parts with diagrams
showing how to replace seals. Or if you do not want to do your own repairs,
there are many qualified shops (including ours) that do this work.
One of the great controversies in the aviation fuel world is whether or not
to have an automatic drain valve. Some people have decided to have a float
operated pilot valve and a discharge valve only. In other words, they want
flow to stop if water collects. The operator then must manually drain out
the water before fuel flow can begin again. If you ever wish to deactivate
an automatic water drain valve and retain normal operation of the discharge
(slug) valve, we offer these words of caution. The vent ports of all brands
of float operated pilot valves must be left open. You must plug ClaVal port
W, Brooks Brodie port A, Baker port C2, Oil Capital port W and Smith port
2. (See GamGram No. 1 0 for additional information.) You must completely
remove the ClaVal and Brooks Brodie automatic drain valves but you need not
do this in the case of other brands.
Do you have float testers on your float operated pilot valves? This handy
little gadget is just an 0-ring sealed screw or plunger that you can open
to cause the float to go up and down while the system is operating With this
device, you can quickly check the automatic drain valve as well as the discharge
valve. Almost all models of float operated valves can be equipped with testers.
Each manufacturer sells a kit with the necessary parts but on some models
you must drill and thread a hole in the valve body.
When did you last test your floats to see if they will float on a fuel/water
interface? Many people now perform this test on a regular schedule. There
are two procedures in use:
Method 1: A hand pump is used to force water in the manual
drain valve. The water is drawn from an open bucket so that you can see exactly
how much water is being used. This method will also allow you to test the
automatic drain valve and the discharge valve.
NOTE: A mechanic recently decided to run this test by using
city water pressure. When I pointed out that the refueler pressure could
be greater than the city pressure, he agreed that people might be unhappy
at finding jet fuel in their kitchen sinks.
Method 2: Remove the float and drop it in a bucket that
has 4 inches (1 0 cm) of fuel on top of 4 inches of water. If the float sinks
in the water, you must return it to the manufacturer to be repaired or replaced.
Leakage is by far the most prevalent complaint regarding filter separator
controls. Many of these complaints are not fully justified because some people
do not understand that a "spit" of fuel is discharged from the vent every
time the system is operated. This is caused by the operation of the diaphragm
in the On-Off pilot valve and amounts to only a few drops. Continuous dripping
is most frequently caused by dirt particles under the seat of the automatic
water drain valve. This is why many operators require that a Y strainer be
located upstream of the drain valve. A very useful device that is often installed
in the discharge line from an automatic water drain valve is a flow indicator.
Many different models are on the market (pin wheels, flappers, jiggling balls,
etc.). In a drain system that is piped to a waste tank, one of these flow
indicators provides a visual indication of discharge flow.
In the next issue of the GamGram, the discharge valve and its pilot controls will be studied.