THE GAMGRAM
Revised Nov. 1996
How many people think that a water slug valve will close because it "senses"
a slug of water? It is amazing how many people believe this but those of
you who read GamGrams 10 and 11, know that the "intelligence" comes from
a device called a "FLOAT OPERATED PILOT VALVE" or an electrical device that
can sense the difference between water and fuel in the sump of a filter
separator.
A very curious thing about slug valves is that people outside of the filter
separator business refer to the very same valve as a diaphragm operated control
valve. The term "slug" was dreamed up many years ago by filter separator
people because it was necessary to stop flow in a fuel system if a "slug"
of water collected in the sump at a rate greater than it could be drained
away. A hydraulic signal to the slug valve (also known as the discharge valve)
will cause it to close to prevent fuel flow until the water level has been
reduced to a safe range.
Sometimes the slug valve is called a RATE OF FLOW CONTROL VALVE. All this
means is that it is a slug valve that was modified to perform both functions.
It can operate as a slug valve and it can also automatically limit the flow
rate to the maximum rating of the filter separator. This is an important
optional function because filter separators are very velocity limited. Note:
If you want to upgrade your slug valve to control flow rate, we can tell
you how to do it, on request.
In Fig. 1, there are two pilot valves shown, X and Z. X is an On-Off pilot
valve and the other (Z) controls the rate of flow. Watts*, Smith, and Oil
Capital make On-Off pilot valves that are similar. Each requires a pressure
signal to cause the slug valve to open. A pilot of this type is shown in
Fig. 2 in the closed position. Note that pressure from the supply port M
is directed to Y, the cover of the slug valve, to close it. In other words,
pressure from M goes through port R, then port J and to port Y on the cover.
If control pressure from the float operated pilot valve is applied at port
L to open the on-off pilot, the slug valve cover is vented through ports
Y, J and N of the on-off pilot into port P. The slug valve then opens because
system inlet pressure at M is greater than outlet pressure at P.
The tricky feature in the On-Off pilot is the orifice shown by an arrow.
If the on-off pilot has been opened to start main valve flow, the orifice
allows a small "pilot flow" from R to bypass the main valve through port
N and then to P. When a rate of flow pilot is added, you can see that by
regulating or throttling this "pilot flow"' the pressure at the slug valve
cover can be regulated to cause the main valve to modulate between the open
and closed positions.
NOTE: In the 1996 revision, these figures have been revised for clarification
*Formerly known as Baker and more recently Muesco.
All manufacturers make rate of flow pilots (Fig. 3) that are almost identical.
To control it, an orifice plate is located at the inlet of the discharge
valve. Pressure taps (G1 and G2) are located at the downstream and upstream
sides of the plate which has a hole in it that is somewhat smaller than the
piping. G1 is the pressure upstream of the orifice plate while G2 is the
pressure after the orifice plate. When flow passes through the orifice, the
pressure loss across the plate becomes greater and greater as the flow rate
increases. In other words, an orifice plate is a simple flow meter. By taking
these two pressures as G1 (high) and G2 (low) to a pilot valve Z, the diaphragm
will move away from the side having the highest pressure. This force is resisted
by a spring, but the tension on the spring can be changed by turning the
screw at the top. This pilot valve will adjust itself to try to maintain
a perfect balance but in so doing, it regulates the amount of "pilot" flow
that can pass through port K. This will influence the pressure that is in
the slug valve cover to modulate flow rate. For example, if the flow through
the orifice plate is too high, its pressure drop is also high. This results
in a partial closing of port K, restricting pilot flow. This causes more
pressure on top of the slug valve diaphragm, causing it to close slightly
to correct the excessive flow rate.
The ClaVal system is exactly the same, except that the On-Off pilot (Fig.
4) works in the reverse of the one in Figure 2. In the position shown, control
pressure is being applied at L. Supply Pressure at R goes thru J and directly
to the slug valve cover through port Y to block fuel flow through the main
(slug) valve. To open the slug valve, L must be vented so that pressure at
R will lift the diaphragm and close port H. The orifice then supplies "pilot"
flow and all other functions are the same as described for other brands.
The slug valve cover is vented through port J to N and then to P.
When slug valve problems occur, our experience has been that diaphragm failures
are the primary cause. These are easy to find. Disconnect the fitting at
Y and turn on the pump. Continuous flow from the slug valve cover means a
diaphragm failure. A failure of the On-Off pilot diaphragm in Figure 2 can
be detected by disconnecting the fittings at N and L. Apply pressure at N
and look for leakage at L. A failure in the rate of flow pilot diaphragm
is found by disconnecting one of the orifice pressure fittings, G1 or G2.
Leakage indicates failure of the diaphragm.
We have reproduced Tables 2 and 3 from GamGram 10 so that you can follow
a typical troubleshooting problem. We cannot review all failure modes for
all brands, but this one shows the reasoning technique. You have ClaVal equipment
and the slug valve will not open. Disconnect the fitting at L in Figure 4.
If flow comes out of the tube, the float is up so water is in the sump and
that is the reason the slug valve will not open. If the automatic water drain
valve will not open, its diaphragm may be found to be leaking and water flow
will be found in the vent tubing from the float valve. If the On-Off pilot
diaphragm had failed, a fuel flow would have been found in the vent before
the fitting at L was disconnected.
|
Port Identification |
ClaVal |
Watts Before 5/86 |
Watts After 5/86 |
Brooks |
Oil Capital |
Smith |
| Supply |
S |
A |
P |
D |
P |
D-9 |
| Water Drain Valve |
W |
C2 |
DV |
A |
W |
A-2 |
| Discharge Valve |
F |
C1 |
SV |
C |
A |
B-5 |
| Vent |
D |
B |
E |
B |
E |
C-6 |
|
Float Position |
ClaVal |
Watts
Before 5/86 |
Watts
After 5/86 |
Brooks |
Oil Capital |
Smith |
ClaVal
CFF12-H3 |
| Up | F-S, W-D | C1-B, C2-A | SV-E, DV-P | C-D, A-B | A-E, W-S | 5-6, 2-9 | F-D, W-S |
| Intermediate | F-D, W-D | C1-A, C2-A | SV-P, DV-P | C-B, A-B | A-S, W-S | 5-9, 2-9 | F-S, W-S |
| Down | F-D, W-S | C1-A, C2-B | SV-P, DV-E | C-B, A-D | A-S, W-E | 5-9, 2-6 | F-S, W-D |
In conclusion, we feel that we should have emphasized in GamGrams 10 and
11 that the Supply fuel should be filtered to prevent malfunctions in the
float pilot. Supply must come from downstream of the coalescers or be separately
filtered. Also, in retrospect, we might have recommended a 40 mesh strainer
upstream of the automatic drain valve. Most leaks from that valve are caused
by dirt in its seat.
Next GamGram || Previous GamGram || GamGram Menu || Gammon Home